Skip to main navigation Skip to search Skip to main content

Seismic qualification and fragility testing of porcelain transformer bushings

  • Pacific Gas and Electric Company

Research output: Contribution to conferencePaperpeer-review

Abstract

Seismic qualification and fragility testing of two 196kV porcelain transformer bushings is discussed. The importance of power transformers in electric substations combined with electric utility experience with past performance of porcelain bushings during earthquakes provided the impetus for performing this work. A new standard for the seismic qualification of electric substation equipment, IEEE 693-1997, has been under development for the past several years, was used as the basis for the testing protocol. This paper describes the mechanisms of structural resistance and failure modes of porcelain bushings, and discusses the random input motion shake table tests performed. Key results and responses are summarized, for shake table testing at levels up to about 2g peak ground acceleration.

Original languageEnglish
Pages663-672
Number of pages10
StatePublished - Aug 1999
EventProceedings of the 1999 5th U.S. Conference on Lifeline Earthquake Engineering: Optimazing Post-Earthquake Lifeline System Reliability - Seattle, WA, USA
Duration: Aug 12 1999Aug 14 1999

Conference

ConferenceProceedings of the 1999 5th U.S. Conference on Lifeline Earthquake Engineering: Optimazing Post-Earthquake Lifeline System Reliability
CitySeattle, WA, USA
Period08/12/9908/14/99

Fingerprint

Dive into the research topics of 'Seismic qualification and fragility testing of porcelain transformer bushings'. Together they form a unique fingerprint.

Cite this