Skip to main navigation Skip to search Skip to main content

PD characteristics of oil-pressboard insulation under AC and DC mixed voltage

  • Junhao Li
  • , Xutao Han
  • , Zehui Liu
  • , Xiu Yao
  • , Yanming Li
  • Xi'an Jiaotong University

Research output: Contribution to journalArticlepeer-review

49 Scopus citations

Abstract

The insulation problem of converter transformers has become one of the core issues in HVDC system, which is receiving more and more attention. A converter transformer has complex structures and requires high insulation level. The voltage waveform which the converter transformer insulation withstands is different from AC transformers. In the valve side of the converter transformer, the insulation endures a mixed voltage of AC voltage, DC voltage, harmonics and the pulsating component etc. Partial discharge (PD) occurring in oil-pressboard insulation is the one of the main causes of insulation breakdown, and it is the main factor of electrical aging of materials. Even though PD characteristics under pure AC or DC voltage waveform have been studied by many researchers, little research has been done with the mixed voltage. In this paper, the AC + DC mixed voltage experiment system is set up to study the PD characteristics under mixed voltage waveforms. The study results indicate that the pressboard withstands most of the DC component and void withstands most of the AC component when applied mixed voltage. For PD inception voltage, it is decided by both the AC component and DC component. For PD development, AC component has more significant influence than DC component. However, the DC component is found to promote PD activity under AC half cycle with the same DC polarity and inhibit PD activity under AC half cycle with the opposite DC polarity. The results in this paper provide an experimental foundation for the converter transformer insulation breakdown mechanism and analysis.

Original languageEnglish
Article number7422590
Pages (from-to)444-450
Number of pages7
JournalIEEE Transactions on Dielectrics and Electrical Insulation
Volume23
Issue number1
DOIs
StatePublished - Feb 2016

Keywords

  • Converter transformer
  • Mixed voltage
  • Oil-pressboard insulation
  • Partial discharge

Fingerprint

Dive into the research topics of 'PD characteristics of oil-pressboard insulation under AC and DC mixed voltage'. Together they form a unique fingerprint.

Cite this