Abstract

In active distribution grids, smart inverters (SI) can provide grid support functionalities through the control of active and reactive power. However, SIs operate based on droops as per the IEEE-1547; therefore, the dispatch setpoints obtained from the distribution grid optimal power (DOPF) models should lie on SIs' droops and abide by the IEEE-1547. Moreover, instead of following rule-based methods or arbitrarily selected settings, the SI settings have to be optimally configured in order to enhance the network performance. The objective of this work is to obtain optimal droop settings of SIs using DOPF formulation for Volt-VAr and Volt-Watt grid-support functions. The non-convexity of the DOPF model as well as the inclusion of droops as constraints into the DOPF model makes this a computationally challenging problem to solve. The problem is formulated as a nonlinear programming problem to minimize the total system losses and voltage deviation. The efficacy of the model is validated on the IEEE 123-node feeder with 15 photovoltaic systems. Case studies demonstrate that optimal SI settings can improve grid performance compared to the recommended default settings.

Original languageEnglish
Title of host publication2021 IEEE 48th Photovoltaic Specialists Conference, PVSC 2021
PublisherInstitute of Electrical and Electronics Engineers Inc.
Pages2584-2589
Number of pages6
ISBN (Electronic)9781665419222
DOIs
StatePublished - Jun 20 2021
Event48th IEEE Photovoltaic Specialists Conference, PVSC 2021 - Fort Lauderdale, United States
Duration: Jun 20 2021Jun 25 2021

Publication series

NameConference Record of the IEEE Photovoltaic Specialists Conference
ISSN (Print)0160-8371

Conference

Conference48th IEEE Photovoltaic Specialists Conference, PVSC 2021
Country/TerritoryUnited States
CityFort Lauderdale
Period06/20/2106/25/21

Keywords

  • IEEE-1547
  • optimal power flow
  • smart inverter
  • Volt-VAr
  • Volt-Watt