Flexural properties of flexible conductors interconnecting electrical substation equipment

  • Madsen, Kneppers and Associates

Research output: Contribution to journalArticlepeer-review

29 Scopus citations

Abstract

This paper presents the results of quasi-static bending tests on two different flexible conductors (cables) used to interconnect electrical substation equipment. The main objectives were to observe the flexural response of flexible conductors and to determine their moment-curvature relationships under axial tension. The results of the tests indicate that the force-displacement behavior of the conductors is linear-elastic with negligible hysteretic response. For most combinations of axial tension and lateral displacement, the flexural stiffness is very small, and tends toward the minimum possible flexural stiffness, corresponding to the situation where all the strands are slipping past each other, and are unable to transfer any shear force. Only for very large axial tension values does the flexural stiffness approach the maximum possible flexural stiffness, corresponding to the situation where all the strands are able to transfer longitudinal shear forces over one another, and the conductor section acts as a solid cross section.

Original languageEnglish
Pages (from-to)151-159
Number of pages9
JournalJournal of Structural Engineering
Volume131
Issue number1
DOIs
StatePublished - Jan 2005

Keywords

  • Axial forces
  • Cables
  • Electric transmission lines
  • Electrical equipment
  • Flexural strength
  • Shear forces

Fingerprint

Dive into the research topics of 'Flexural properties of flexible conductors interconnecting electrical substation equipment'. Together they form a unique fingerprint.

Cite this