Experimental evaluation of occupancy-based energy-efficient climate control of VAV terminal units

  • Jonathan Brooks
  • , Siddharth Goyal
  • , Rahul Subramany
  • , Yashen Lin
  • , Chenda Liao
  • , Timothy Middelkoop
  • , Herbert Ingley
  • , Laura Arpan
  • , Prabir Barooah
  • University of Florida
  • University of Missouri

Research output: Contribution to journalArticlepeer-review

24 Scopus citations

Abstract

Results are presented from a nearly week-long experimental evaluation of a scalable control algorithm for a commercial building HVAC system based on real-time measurements of occupancy obtained from motion detectors. The control algorithm decides air flow rate and amount of reheat for each variable air volume terminal box based on real-time measurements of occupancy and space temperature. It is a rule-based controller, so the control computations are simple. The experiments showed that the proposed controller resulted in 37% energy savings over baseline on average without sacrificing indoor climate. In contrast to prior work that reports energy savings without a careful measure of the effect on indoor climate, it is verified that the controller indeed maintains indoor climate as well as the building’s baseline controller does. This verification is performed from measurements of a host of environmental variables and analysis of before/after occupant survey results. A complete system required to retrofit existing buildings with the controller is presented, which includes a wireless sensor network and a software execution platform. Two useful observations from this work are: (i) considerable energy savings—along with compliance with ASHRAE ventilation standards—are possible with simple occupancy-based control algorithms that are easy to retrofit; and (ii) these savings are attained with binary occupancy measurements from motion detectors that do not provide occupancy-count measurements. Results also show that there is a large variation in energy savings from zone to zone and from day to day.

Original languageEnglish
Pages (from-to)469-480
Number of pages12
JournalScience and Technology for the Built Environment
Volume21
Issue number4
DOIs
StatePublished - 2015

Fingerprint

Dive into the research topics of 'Experimental evaluation of occupancy-based energy-efficient climate control of VAV terminal units'. Together they form a unique fingerprint.