Abstract
This paper investigates experimentally the dynamic interaction between components of electrical substation equipment interconnected by flexible (cable) conductors. Shake table tests were conducted on five different pairs of generic substation equipment specimens interconnected by three different flexible conductors with three different levels of slackness. No damage to any of the three flexible conductors was observed during all the seismic tests conducted. Two different types of dynamic responses were observed during the seismic tests. The first type involves low interaction between the interconnected equipment due to a large slack and/or low intensity ground motions. For this case, very different frequency contents between the relative displacement, absolute acceleration, and force response of each equipment item were observed. Also, the large horizontal movement of the more flexible equipment was transferred almost entirely into a vertical motion of the conductor with little transmission to the more rigid equipment. The second type of dynamic response involves high interaction between the interconnected equipment due to a small slack and/or high intensity ground motions. For this case, large vertical acceleration pulses were observed at mid-span of the conductor.
| Original language | English |
|---|---|
| Pages | 667-676 |
| Number of pages | 10 |
| DOIs | |
| State | Published - 2003 |
| Event | Proceedings of the Sixth U.S. Conference and Workshop on Lifeline Earthquake Engineering - Long Beach, CA, United States Duration: Aug 10 2003 → Aug 13 2003 |
Conference
| Conference | Proceedings of the Sixth U.S. Conference and Workshop on Lifeline Earthquake Engineering |
|---|---|
| Country/Territory | United States |
| City | Long Beach, CA |
| Period | 08/10/03 → 08/13/03 |
Fingerprint
Dive into the research topics of 'An Experimental Study on the Seismic Response of Electrical Substation Equipment Interconnected by Flexible Conductors'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver